Monthly Summary Report

EPL Number: 761
EPL Holder: Delta Electricity
EPL Name of facility: VALES POINT POWER STATION AND COAL UNLOADER
EPL Address of facility: OFF VALES POINT ROAD, MANNERING PARK, NSW, 2259
EPL Website link: http://www.environment.nsw.gov.au/prpoeoapp/ViewPOEOLicence.aspx?DOCID=32011&SYSUID=1&LICID=761
EPL Monitoring locations: http://www.de.com.au/ArticleDocuments/202/Environment%20Protection%20Licence%20Locations%20Vales%20Point.pdf.aspx
EPL Unit of measure abbreviations http://www.de.com.au/ArticleDocuments/202/Environment%20Protection%20Licence%20Units%20of%20Measurement%20Vales%20Point.pdf.aspx
EPL Period monitored: September 2013
Monthly Summary Status: Complete: all monitoring data obtained
   
Licenced Monitoring Point Code Pollutant Unit of Measure Monitoring Frequency Number of times monitored in month Min. Value Mean Value Median Value Max. Value 100 Percentile limit Exceedance Published Date Comment
LDP1 Chlorine (free residual) mg/L Monthly 1 0.14 0.14 0.14 0.14 0.2 No 14/10/2013  
LDP1 Oil and Grease Visible Continuous Continuous 0 0 0 0   No 14/10/2013  
LDP1 Temperature - daily - hourly average oC Continuous Continuous 24.1 26.9 27.2 29.3 37.5 No 14/10/2013  
LDP1 Temperature - daily - hourly maximum oC Continuous Continuous 25.7 28.7 29.5 31.2 37.5 No 14/10/2013  
LDP11 Nitrogen Oxides - daily - hourly average mg/m3 Continuous Continuous 749 813 816 860 1500 No 14/10/2013  
LDP11 Nitrogen Oxides - daily - hourly maximum mg/m3 Continuous Continuous 851 914 907 1014 1500 No 14/10/2013  
LDP11 Sulphur dioxide - daily - hourly average ppm Continuous Continuous 242 275 277 291 600 No 14/10/2013  
LDP11 Sulphur dioxide - daily - hourly maximum ppm Continuous Continuous 269 294 294 311 600 No 14/10/2013  
LDP11 Undifferentiated Particulates - daily - hourly average g/m3 Continuous Continuous 0.019 0.023 0.024 0.032   No 14/10/2013  
LDP11 Undifferentiated Particulates - daily - hourly maximum g/m3 Continuous Continuous 0.022 0.026 0.024 0.033   No 14/10/2013  
LDP12 Nitrogen Oxides - daily - hourly average mg/m3 Continuous Continuous 863 979 985 1064 1500 No 14/10/2013 Unit 6 planned outage during September.
LDP12 Nitrogen Oxides - daily - hourly maximum mg/m3 Continuous Continuous 1104 1154 1144 1243 1500 No 14/10/2013 Unit 6 planned outage during September.
LDP12 Sulphur dioxide - daily - hourly average ppm Continuous Continuous 226 260 259 292 600 No 14/10/2013 Unit 6 planned outage during September.
LDP12 Sulphur dioxide - daily - hourly maximum ppm Continuous Continuous 280 326 333 367 600 No 14/10/2013 Unit 6 planned outage during September.
LDP12 Undifferentiated Particulates - daily - hourly average g/m3 Continuous Continuous 0.023 0.025 0.025 0.028   No 14/10/2013 Unit 6 planned outage during September.
LDP12 Undifferentiated Particulates - daily - hourly maximum g/m3 Continuous Continuous 0.025 0.031 0.032 0.039   No 14/10/2013 Unit 6 planned outage during September.
LDP18 Ammonia mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Cadmium mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Copper mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Lead mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Manganese mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Nitrate + nitrite (oxidised nitrogen) mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Nitrogen (total) mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 pH pH Daily during any discharge > 2 hrs           6.5 to 9 No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Phosphorus (total) mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Selenium mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Total Kjeldahl Nitrogen mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Total suspended solids mg/L Daily during any discharge > 2 hrs           50 No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP18 Zinc mg/L Daily during any discharge > 2 hrs             No 14/10/2013 Not sampled: due to no flow / no discharge.
LDP2 Nitrate + nitrite (oxidised nitrogen) mg/L Monthly 1 0.02 0.02 0.02 0.02   No 14/10/2013  
LDP2 pH pH Monthly 1 8.8 8.8 8.8 8.8 6.5 to 9.5 No 14/10/2013  
LDP2 Phosphorus (total) mg/L Monthly 1 0.25 0.25 0.25 0.25   No 14/10/2013  
LDP2 Reactive Phosphorus mg/L Monthly 1 0.12 0.12 0.12 0.12   No 14/10/2013  
LDP2 Total suspended solids mg/L Fortnightly 2 5 10.5 10.5 16 50 No 14/10/2013  
LDP4 Nitrate + nitrite (oxidised nitrogen) mg/L Monthly 1 0.34 0.34 0.34 0.34   No 14/10/2013  
LDP4 pH pH Monthly 1 8.4 8.4 8.4 8.4   No 14/10/2013  
LDP4 Phosphorus (total) mg/L Monthly 1 0.01 0.01 0.01 0.01   No 14/10/2013  
LDP4 Total suspended solids mg/L Monthly 1 43 43 43 43 50 No 14/10/2013  


Monthly Exceedance Table

EPL Number: 761
EPL Holder: Delta Electricity
EPL Name of facility: VALES POINT POWER STATION AND COAL UNLOADER
EPL Address of facility: OFF VALES POINT ROAD, MANNERING PARK, NSW, 2259
EPL Website link: http://www.environment.nsw.gov.au/prpoeoapp/ViewPOEOLicence.aspx?DOCID=32011&SYSUID=1&LICID=761
EPL Monitoring locations: http://www.de.com.au/ArticleDocuments/202/Environment%20Protection%20Licence%20Locations%20Vales%20Point.pdf.aspx
EPL Unit of measure abbreviations http://www.de.com.au/ArticleDocuments/202/Environment%20Protection%20Licence%20Units%20of%20Measurement%20Vales%20Point.pdf.aspx
EPL Period monitored: September 2013
   
Sample Date Licenced Monitoring Point Code Pollutant Unit of Measure Sample Value 100 Percentile Limit Exceedance Comment
NIL NIL NIL NIL NIL NIL NIL NIL


Monthly Correction Log

EPL Number: 761
EPL Holder: Delta Electricity
EPL Name of facility: VALES POINT POWER STATION AND COAL UNLOADER
EPL Address of facility: OFF VALES POINT ROAD, MANNERING PARK, NSW, 2259
EPL Website link: http://www.environment.nsw.gov.au/prpoeoapp/ViewPOEOLicence.aspx?DOCID=32011&SYSUID=1&LICID=761
EPL Monitoring locations: http://www.de.com.au/ArticleDocuments/202/Environment%20Protection%20Licence%20Locations%20Vales%20Point.pdf.aspx
EPL Unit of measure abbreviations http://www.de.com.au/ArticleDocuments/202/Environment%20Protection%20Licence%20Units%20of%20Measurement%20Vales%20Point.pdf.aspx
EPL Period monitored: September 2013
   
Sample Date Licenced Monitoring Point Code Pollutant Unit of Measure Original Data Corrected Data Date Corrected Date Originally Published Reason
NIL NIL NIL NIL NIL NIL NIL NIL